Dry Distribution Transformer

The Dry Distribution Transformer range includes SCH15 amorphous-core models and SCB10/SCB11 epoxy-cast silicon-steel models for indoor medium-voltage distribution. These oil-free transformers supply plant switchboards, commercial buildings, hospitals and transport infrastructure. The range is intended for consulting engineers, switchgear integrators and building-system contractors selecting between reduced core losses and conventional cast-resin construction.
Send Inquiry
Description

Product Overview

 

The Dry Distribution Transformer range includes SCH15 amorphous-core models and SCB10/SCB11 epoxy-cast silicon-steel models for indoor medium-voltage distribution. These oil-free transformers supply plant switchboards, commercial buildings, hospitals and transport infrastructure. The range is intended for consulting engineers, switchgear integrators and building-system contractors selecting between reduced core losses and conventional cast-resin construction.

 

Key Features

 

Choice of Amorphous or Laminated Core

SCH15 units use a wound amorphous-alloy magnetic circuit, while SCB10/SCB11 units use laminated grain-oriented silicon steel. When the substation remains energized for many low-demand hours, the core material influences no-load electricity consumption; the appropriate choice follows guaranteed loss values for the specified duty.

Dry-Type Electrical Insulation

The dry distribution transformer range avoids insulating oil. For indoor transformer rooms, this removes the need for liquid dielectric piping and routine oil sampling, although equipment clearances, ventilation and local fire-system requirements still govern the installation.

Series-Specific Winding Construction

The SCH15 design uses fiberglass-reinforced epoxy insulation around the high-voltage winding; the SCB10/SCB11 design uses copper-foil low-voltage windings and cast-resin high-voltage insulation. In applications with cyclic loads, the winding geometry and support system address mechanical movement and insulation stress differently in each series.

Temperature Monitoring for Indoor Substations

The dry-type range supports winding-temperature monitoring with alarms and trip signaling. For substations that operate outside normal staffing hours, a correctly wired controller provides a protection signal when the measured winding temperature reaches its configured limit.

 

Customization Capability

 

The SCH15 and SCB series are configured from the same project rating schedule but retain their respective magnetic-core and insulation designs. The selected model, electrical connections and mechanical layout are confirmed against the intended installation before manufacture.

Customizable Items 

• SCH15, SCB10 or SCB11 product family
• Rated capacity and primary voltage
• Secondary voltage and vector group
• Efficiency/loss specification for the selected core

• Tap range and impedance
• Winding conductor and insulation requirement
• Indoor enclosure and airflow arrangement
• Monitoring contacts, terminal direction and labeling

 

Technical Specifications

 

Item

SCH15 Amorphous Alloy Dry-Type Transformer

SCB10 / SCB11 Epoxy Resin Cast Dry-Type Transformer

Application

Indoor use only

Indoor use only; can be installed at load centers

Installation Altitude

≤1000 m

≤1000 m

Ambient Temperature

-25°C to +40°C; avg hottest month +30°C; annual avg +20°C

Max +40°C; daily avg +30°C; annual avg +20°C; min -20°C

Power Supply Requirements

Approximately sinusoidal waveform; balanced three-phase system; no significant contamination

Approximately sinusoidal waveform; balanced multi-phase system

Core Structure

Amorphous alloy strip-wound core; rectangular section; four-frame five-leg / three-frame three-leg structure

Grain-oriented cold-rolled silicon steel; 45° step-lap joints; resin-coated surface

Winding Structure

Low-voltage copper winding; high-voltage H-class enamel wire with fiberglass-reinforced epoxy encapsulation

Low-voltage copper foil winding; F-class insulation; epoxy resin sealed winding ends

Temperature Control

Built-in temperature monitoring module

BWDK series temperature controller with scanning measurement, over-temperature alarm, and trip protection

Voltage Regulation

No-load and on-load tap changing available

Not applicable

Vector Group

Dyn11 or Yyn0

Not applicable

Insulation Level

LI75AC35 / AC5

Not applicable

Rated Voltage

HV: 6 / 6.3 / 6.6 / 10 / 10.5 / 11kV; LV: 0.4kV

HV: 10kV class; LV: 0.4kV

Standards

GB1094.1-2013, GB1094.11-2007, GB/T10228-2015

National standards for dry-type power transformers

 

product-1000-716

product-1000-623

 

Why Choose Us

 

Nuo'an supplies more than one dry-type core technology through its own transformer manufacturing operation, allowing different model requirements to be coordinated within a single project order. The factory accepts orders containing different models.
Its internal R&D team, 108-person workforce and organized assembly operation support technical drawing review and scheduled manufacturing. Customers receive contract-based delivery coordination and a one-year warranty.

 

Quality Control

 

Incoming checks are separated by series: amorphous strip for SCH15 designs, grain-oriented silicon-steel laminations for SCB designs, plus relevant copper and insulation materials for both. Component identification is matched against the order-specific build documents.
During manufacture, the SCH15 assembly is checked for core integrity and reinforced insulation; the SCB cast coils are reviewed after resin processing for visible surface defects and dimensional accuracy. Both are inspected for terminal clearances and support security.
Final inspection checks rated connections, resistance, no-load and load-loss performance, impedance, insulation and the agreed monitoring functions. Finished transformers are examined before packing, with independent witnessing accepted by arrangement.

 

FAQs

 

Q: How is delivery time determined for standard models?

A: By the required quantity and confirmed production schedule.

Q: Which export packaging is available?

A: Wooden cases, pallets or cartons, according to the unit and shipment.

Q: Are SCH15 and SCB units interchangeable without an engineering review?

A: No. Verify footprint, losses, impedance, connections and protection settings first.

Q: What if phase loading is substantially unbalanced?

A: Keep each phase within its rating and verify the neutral-system design.

Hot Tags: dry distribution transformer, China dry distribution transformer manufacturers, suppliers, factory, Amorphous Core Type Distribution Transformer, Amorphous Oil Immersed Transformer, Cast Resin Distribution Transformer, Dry Distribution Transformer, Energy Efficient Distribution Transformers, Oil Filled Distribution Transformers